Development of Hardware and Monitoring Software for Stable Operation of Fire Pumps 


Vol. 37,  No. 4, pp. 28-35, Aug.  2022
10.14346/JKOSOS.2022.37.4.28


PDF
  Abstract

This study is aimed to develop a safety diagnosis system for fire pumps that detects normal and abnormal signals for the stable operation of the system. Hence, the following activities were carried out: first, a threshold value was identified for the normal operation and six abnormal operations (adherence of impeller, absence of water source, separation of pump and motor, run-stop operation, air inflow into the casing, and reverse-phase loss of the power line) reflecting changes in the current, flow and pressure of fire pumps; secondly, based on the identified signals, an algorithm capable of detecting three abnormal signals was developed and in terms of hardware, a current, pressure and flow sensor suitable for the analogue input values of NI-6009 was designed and installed. This combination of the hardware and software is applicable as a diagnosis system to ensure the stable operation of fire pumps.