An Experimental Study on Improvement of Fire Extinguishing Performance of Basic Sprinkler System 


Vol. 33,  No. 3, pp. 46-51, Jun.  2018
10.14346/JKOSOS.2018.33.3.46


PDF
  Abstract

A basic sprinkler system is a fire extinguishing system that can be easily installed in a fire-vulnerable place such as a publicly used establishments. However, the publicly used establishments are not only complicated in structure, but also have a large amount of flammable interior materials, and the users are not normally in a normal state, which is a very dangerous fire-fighting object. Therefore, due to the low fire extinguishing performance of the basic sprinkler system installed in the publicly used establishments, the fire suppression control can not be performed quickly in case of fire, which may increase the life and property damage. In this study, the cases of quantitative changes of extinguishing water used in basic sprinkler system and the cases of addition of additives such as wetting agents, reinforced agents to improve extinguishing performance were compared. Experimental results showed that the extinguishing performance was improved as the quantity of extinguishing water increase and the reinforced agents showed similar performance to that of 60% increase in the amount of extinguishing water. The cooling time to 200℃ and oxygen concentration were improved up to 14.3% and 34.5%, respectively. In the case of using the wetting agent, the cooling time to 200℃ and oxygen concentration did not show any significant improvement, but showed the effect of preventing deep seated fire. In order to prevent loss of life and property, it is necessary to improve the performance of the basic sprinkler system by increasing amount of extinguishing water or using additives like reinforced agents.

  Statistics
Cumulative Counts from November, 2022
Multiple requests among the same browser session are counted as one view. If you mouse over a chart, the values of data points will be shown.


  Cite this article

[IEEE Style]

허민녕 and 신창섭, "An Experimental Study on Improvement of Fire Extinguishing Performance of Basic Sprinkler System," Journal of the Korean Society of Safety, vol. 33, no. 3, pp. 46-51, 2018. DOI: 10.14346/JKOSOS.2018.33.3.46.

[ACM Style]

허민녕 and 신창섭. 2018. An Experimental Study on Improvement of Fire Extinguishing Performance of Basic Sprinkler System. Journal of the Korean Society of Safety, 33, 3, (2018), 46-51. DOI: 10.14346/JKOSOS.2018.33.3.46.